When disinfecting a piped water supply by chlorination, the recommended minimum free residual chlorine at the end of the contact period is:
- 2 mg/L after 30 minutes of contact
- 5 mg/L after 1 hour of contact
- 0.2 mg/L after 10 minutes of contact
- 0.5 mg/L after 1 hour of contact (Correct Answer)
Explanation
Chlorination principles (Park). The water should be clear and free from turbidity. Chlorine demand, the amount used up by organic matter, ammonia and reducing agents, must be met first. Chlorine added beyond the breakpoint gives free residual chlorine, which is the effective disinfectant. In water, chlorine forms hypochlorous acid (HOCl, the main disinfectant, about 70–80 times more germicidal than OCl⁻, and favoured at pH around 7). The standard recommendation is a minimum free residual chlorine of 0.5 mg/L after a contact period of at least 1 hour. This kills bacteria and viruses (most vegetative bacteria are killed at lower levels, but viruses need this level). It also leaves a residual that protects against recontamination in the distribution pipes. At consumer taps, a residual of about 0.2 mg/L is generally acceptable. Chlorine does not reliably kill cysts (Giardia, Entamoeba histolytica), Cryptosporidium oocysts, helminth ova or spores at these concentrations. Residual chlorine is measured with the orthotolidine (OT) test, which measures free and combined chlorine, or the orthotolidine–arsenite (OTA) test, which separates free chlorine from combined chlorine and interfering substances. Superchlorination is used for heavily polluted water and is then dechlorinated. During outbreaks in Nepal, households are often given chlorine solutions (for example 'Piyush') for water treatment. Reference: Park PSM (environment and health).