The minimum free residual chlorine recommended after one hour of contact in disinfected drinking water is:
- 0.2 mg/L
- 0.5 mg/L (Correct Answer)
- 1.0 mg/L
- 2.0 mg/L
Explanation
Chlorination is effective only when chlorine demand is fully met and a free residual remains. The recommended minimum is a free residual chlorine of 0.5 mg/L after a contact period of at least one hour, which kills bacteria and most viruses. Break-point chlorination is the point at which chlorine demand is satisfied and free residual chlorine starts to appear. Chlorine acts mainly as hypochlorous acid (HOCl), which is about 70-80 times more germicidal than the hypochlorite ion. It works best at pH 7 and less well in alkaline water. Chlorine does not reliably kill cysts (Entamoeba, Giardia), Cryptosporidium, helminth ova, and some viruses such as hepatitis A and polio at usual doses, so higher doses (super-chlorination) may be needed during outbreaks. The orthotoluidine test measures free and combined chlorine, and the orthotoluidine-arsenite test separates them. For well disinfection, bleaching powder (33% available chlorine) is calculated with Horrock's apparatus. At the consumer tap, a residual of at least 0.2 mg/L is expected.