For effective disinfection of a piped community water supply, WHO recommends that the free residual chlorine should be at least:

31 views
  • 0.2 mg/L after a contact period of 10 minutes
  • 1.0 mg/L after a contact period of 60 minutes
  • 5.0 mg/L after a contact period of 5 minutes
  • 0.5 mg/L after a contact period of at least 30 minutes (Correct Answer)

Explanation

Chlorine destroys bacteria and viruses only after its chlorine demand (reaction with organic matter, ammonia and other substances) has been satisfied; the chlorine left over is the free residual chlorine. WHO recommends a free residual chlorine concentration of at least 0.5 mg/L after a minimum contact time of 30 minutes (at pH below 8) for centralized disinfection. The presence of free residual chlorine also gives protection against re-contamination in the distribution system, and its measurement with an orthotoluidine or DPD test is a simple field check of water safety. A level of 0.2 mg/L with only 10 minutes of contact is inadequate for central treatment, although 0.2 mg/L is often used as the minimum residual at the consumer's tap. A level of 1.0 mg/L after 60 minutes is more than required for routine practice and causes taste complaints. A concentration of 5 mg/L applies to super-chlorination or disinfection of wells after floods, not to routine treatment, and a 5-minute contact time is too short.