A 3-phase, 4-wire system is supplying a balanced load of 100 kW at 0.8 power factor lagging. The line-to-line voltage is 415 V. What is the current flowing through each phase conductor?
17 views
- 170 A (Correct Answer)
- 200 A
- 230 A
- 250 A
Explanation
To calculate the current flowing through each phase conductor, we can use the formula:
I = P/(√3 x V x pf)
where I is the current, P is the power, V is the line-to-line voltage, pf is the power factor, and √3 is the factor to account for the three phases.
In this case, P = 100 kW, V = 415 V, and pf = 0.8. Substituting the values, we get:
I = 100,000/(√3 x 415 x 0.8) = 170 A (approx.)
Therefore, the correct answer is (a) 170 A.